Testing Heating Elements

How to Test the Heating Element in a Furnace

Learn how to test an electric furnace heating element safely: shut off power, inspect it, check it with a multimeter, and know what the readings mean.

On this page
  1. Short answer
  2. Which furnaces have a heating element
  3. Safety before you start
  4. Tools you need
  5. Step 1: Inspect the element
  6. Step 2: Photograph and disconnect the wires
  7. Step 3: Check for an open circuit
  8. Step 4: Compare the reading to the rated resistance
  9. Step 5: Check for a ground fault
  10. Step 6: Rule out the parts that can mimic a dead element
  11. What the results mean
  12. When to call a professional
  13. Gas furnaces: what to check instead
  14. Summary

Short answer

To test a furnace heating element, shut off power to the furnace at the breaker, confirm the power is off, and disconnect the element. Then check it with a multimeter. An element that gives no reading at all (an open circuit) has usually burned out. An element that shows continuity to the metal frame is grounded. In both cases the element needs replacing. Before you condemn it, check the high-limit switch, fuses and relay, because these can stop the heat in the same way.

This guide covers electric furnaces. Gas furnaces don’t have a heating element, so these steps don’t apply to them.

Which furnaces have a heating element

Electric furnaces heat air by passing current through metal elements in the airflow. These elements are often called heat strips. Most units have several, and they switch on in stages as the house needs more heat. Some heat pump systems also use strips as backup heat, sometimes called auxiliary or emergency heat.

Gas furnaces heat with a burner and an igniter instead. If you’re not sure which type you have, read how to know if furnace is gas or electric before you open anything. A gas supply line and a flue pipe on the furnace point to a gas unit. Electric units usually have no flue.

Safety before you start

Electric furnaces usually run on 240 volts, which can cause serious injury or death. Before you open the cabinet:

  • Turn the thermostat to Off.
  • Switch off the furnace’s power switch, if it has one.
  • Turn off the breaker that feeds the furnace, and tape a note over it so no one switches it back on. If the breaker label is hard to read, check what amp breaker does a furnace need against the unit’s rating label.
  • Confirm the power is off with a non-contact voltage tester, both at the furnace’s power supply and at the element terminals, before you touch anything.
  • Let the elements cool. They can stay hot for a while after the furnace shuts down.

If you can’t confirm the power is off, or you’re not comfortable around 240-volt wiring, stop and call a qualified technician.

Tools you need

  • A digital multimeter with resistance (ohms) and continuity settings
  • A non-contact voltage tester
  • Nut drivers or a screwdriver set for the access panel
  • A flashlight
  • Your phone, to photograph the wiring before you disconnect anything

Step 1: Inspect the element

Remove the access panel on the heating section and look over the elements. You’re checking for:

  • Blisters, cracks, sagging coils, or dark scorch marks on the element or the nearby metal
  • Melted, brittle or discolored wire insulation
  • Loose or burned terminal connections
  • Heavy dust or debris on the strips

Dust can cause a burning smell the first time the furnace runs in a season. A strong or lingering smell is a reason to look more closely. If you see scorched or melted wiring, stop and call a technician rather than continuing to test around damaged wiring.

Step 2: Photograph and disconnect the wires

Take a photo of the wiring before you disconnect anything, and label each wire by its position. What color wires go where on a furnace varies by brand, so don’t rely on colors alone. Then remove the wires from the element terminals and keep them clear of the metal frame while you test.

Step 3: Check for an open circuit

Set the multimeter to the resistance setting (ohms, Ω). Use a low range if your meter has one. Touch one probe to each terminal of the element.

  • A number on the display means the element has a complete path for current. That’s expected for a working element.
  • OL, a blank reading, or no continuity means an open circuit. The element has likely burned through and needs replacing.

Step 4: Compare the reading to the rated resistance

The element’s label lists its rated watts and voltage, and sometimes only the watts. You can estimate the expected resistance with this formula:

R = V² ÷ W

Resistance in ohms equals volts squared divided by watts. For example, a 5,000-watt element on 240 volts works out to about 11.5 ohms (240 × 240 = 57,600, and 57,600 ÷ 5,000 = 11.52).

The rated watts describe the element at operating temperature. A cold element usually reads somewhat lower than the calculated value, so treat the calculation as a rough benchmark, not a precise pass or fail line.

  • A reading close to the calculated value suggests the element is intact.
  • A reading far below it can point to a short inside the element.
  • A reading far above it, or no reading at all, can point to a broken element or a bad connection.

Step 5: Check for a ground fault

A grounded element touches the metal frame or sheath. That’s a shock and fire risk, so check for it even if the element still heats.

Set the multimeter to continuity, or to the highest resistance range. Touch one probe to an element terminal and the other to the metal frame of the heating section. Test each terminal separately.

  • No beep and an OL or very high reading mean the element isn’t grounded.
  • A beep or a low reading means it’s touching metal. Replace the element, and don’t put it back into service.

Step 6: Rule out the parts that can mimic a dead element

Heat can stop without a bad element. Check these before you order a new one:

  • High-limit switch. This safety switch opens if the furnace overheats, which cuts the heat. With power off and the wires disconnected, a working switch should show continuity when it’s cool. Some switches have a manual reset button. If one trips repeatedly, find out why. A dirty filter, a blocked return or a blower problem is more likely than a faulty switch.
  • Fuses. Many electric furnaces have a fuse in the control circuit or the heating section. A blown fuse can mean a shorted element or a wiring fault. Replacing the fuse without finding the cause can blow it again.
  • Relay or sequencer. The relay or sequencer switches each stage of heat strips on. A failed relay can stop one stage even when the element is fine. Testing these safely usually takes a technician.

If the whole furnace has stopped, a wider look at electric furnace not working can help narrow the cause before you start testing strips.

What the results mean

What you find Likely meaning
Resistance near the calculated value, no ground The element is probably intact. Check the limit switch, fuses and relay.
OL or no reading Open circuit. The element has likely burned out.
Reading far below the calculated value Possible internal short. Replace the element.
Continuity to the metal frame Grounded. Replace the element and find out what caused it.

When to call a professional

Call a licensed HVAC technician if any of these apply:

  • The breaker trips when the furnace runs, or trips again soon after you reset it
  • You find scorched, melted or loose wiring
  • You’re not comfortable working with 240-volt power
  • The element is bad and you need a matching replacement part, or you want to keep a warranty in place
  • The high-limit switch or relay tests as bad

Gas furnaces: what to check instead

Gas furnaces don’t have heating elements. They heat with a gas burner, lit by an igniter and monitored by a flame sensor. A gas furnace that won’t heat needs a different check. Gas and combustion problems carry fire and carbon monoxide risks, so have a qualified technician look at them.

Summary

Testing an electric furnace heating element comes down to safety first, then a visual check, then a multimeter test for an open circuit and a ground fault. Compare the readings with the element’s rated resistance, and check the limit switch, fuses and relay before you replace a strip.