The short answer
To size a duct, divide the airflow it must carry by the air speed you choose. That gives the duct’s cross-sectional area. Convert the area into a round diameter or a rectangular width and height, then round up to a standard size. The airflow number has to come from a load calculation or, for a rough check, a rule of thumb.
What CFM means
CFM stands for cubic feet per minute. It measures how much air moves through a duct each minute. Air speed is usually given in feet per minute (FPM). The two are linked through the duct’s area:
CFM = FPM × area in square feet
Rearranged for sizing:
Area in square feet = CFM ÷ FPM
Where the CFM number comes from
For each room, airflow is normally based on the room’s heating or cooling load. A load calculation such as ACCA Manual J gives those loads, and the duct design turns them into airflow at each register.
For a rough whole-system estimate, many installers start from about 400 CFM per ton of cooling. One ton of cooling equals 12,000 BTU per hour. A system rated at 2 tons would therefore land near 800 CFM as a starting figure. Treat this only as a first estimate. The real airflow depends on the house, the equipment and the layout.
Turning CFM into duct size
- Find the airflow the duct must carry, in CFM.
- Choose a target air speed for that run, in FPM. The right choice depends on the design limits for noise and pressure, so use the figures from your design method rather than a number from this article.
- Divide CFM by FPM to get the area in square feet.
- Convert that area into a duct size.
For a round duct, the area in square feet is:
Area = π × (diameter ÷ 2)² ÷ 144
Here the diameter is in inches. Dividing by 144 converts square inches to square feet. To go the other way, from an area in square inches to a diameter, use diameter = the square root of (4 × area ÷ π).
For a rectangular duct, multiply the width by the height in inches and divide by 144 to get square feet.
A worked example
Suppose a branch run must carry 150 CFM, and the design target is 600 FPM. That speed is an example for this calculation, not a recommended standard.
- Area = 150 ÷ 600 = 0.25 square feet, which is 36 square inches.
- Diameter = the square root of (4 × 36 ÷ π), or about 6.8 inches.
- The nearest standard round size is 7 inches. Rounding up lowers the air speed and the pressure loss.
- Check the result. A 7-inch round duct has an area of about 0.27 square feet. At 150 CFM that works out to about 560 FPM, which is under the 600 FPM target.
Why the calculation is only a starting point
- Fittings add resistance. Elbows, takeoffs, boots and transitions cause pressure loss on top of the straight run. Design methods account for them as extra equivalent length.
- Length matters. A long run loses more pressure than a short one, even at the same size.
- The blower sets the limit. An air handler moves a given amount of air only against a given amount of resistance. The manufacturer’s airflow table shows how much air it delivers at a given static pressure.
- Calculators depend on their inputs. An online calculator can be a useful check, but only if it is given the right airflow and the true run length.
Return ducts
The same airflow arithmetic applies to return ducts. If you are wondering how big should my return duct be, start with the airflow it has to carry. Undersized returns are common, and a return that is too small raises the pressure the blower works against.
When to get a professional design
A duct that looks right on paper can still fall short in a real house. Ask for a design or a check when you add rooms, replace equipment, or notice rooms that never get enough air. A technician can measure airflow and static pressure to confirm how the system actually performs.