Static Pressure

How to Measure External Static Pressure in HVAC

A manometer measures external static pressure on the supply and return sides. Here is how to take the readings, combine them and compare them with the rating.

On this page
  1. The Short Answer
  2. What You Need
  3. Before You Measure
  4. Taking the Readings
  5. Reading the Result
  6. Common Mistakes
  7. Safety
  8. When to Call a Technician

The Short Answer

External static pressure is measured with a manometer. You take one reading on the supply side and one on the return side while the system is running, then combine the two. Compare the result with the maximum rated external static pressure in the equipment’s manual. Most homeowners leave this test to a technician, because it needs access points and careful setup.

What You Need

  • A manometer. A digital model or a water-column gauge with pressure hoses will both work.
  • Access points on the supply and return sides. Many systems have test ports on the plenums. If yours does not, a technician can create one safely.
  • The rated external static pressure from the manual or spec sheet.

Before You Measure

  • Confirm the filter is clean and installed. A filter removed during the test gives a lower reading than the system normally sees.
  • Open all supply registers and return grilles, and clear anything blocking them.
  • Run the system at the speed it normally uses. Multi-speed and variable-speed systems can show different readings at different speeds, so note which setting you tested.
  • Let the system run for several minutes so the readings settle.

Taking the Readings

  1. Supply side. Measure the positive pressure in the supply plenum, after the blower.
  2. Return side. Measure the negative pressure on the return side, before the air reaches the blower.
  3. Combine. Add the two readings as absolute values. For example, a supply reading of 0.30 in. w.c. and a return reading of -0.20 in. w.c. gives 0.50 in. w.c. of external static pressure.

Reading the Result

Compare the total with the rating:

  • At or below the rating. Resistance is within the expected range.
  • Close to the rating. Look for restrictions, and retest after any fix.
  • Above the rating. The system is restricted. Fix the most likely cause first, such as a dirty filter, and measure again. If the reading stays high, have a technician inspect the ducts and coil.

Common Mistakes

  • Measuring with the filter removed, which hides the resistance the blower normally works against.
  • Testing with supply registers closed.
  • Comparing the reading with the rating for a different model or speed.
  • Reading only one side, which gives an incomplete picture.
  • Leaving test ports open after the test. Seal them when you finish.

Safety

Turn the system off before you open any panel, and keep hands and tools clear of the blower wheel and electrical parts. Do not work on gas burners or gas controls. If a reading requires the system to run with a panel open, let a trained technician do it.

When to Call a Technician

Call a licensed HVAC technician if you cannot reach the test ports, if the reading is above the rating, or if the system has repeated airflow problems. A technician can also check the coil, the blower and the duct layout that makes up the air distribution system in HVAC.